DT-5554 RCD TESTER
Professional Microprocessor-Controlled Residual Current Device Tester
The DT-5554 RCD Tester is custom microprocessor controlled for highest accuracy and reliability in testing Residual Current Devices (RCDs). This professional instrument provides comprehensive testing of RCD trip times, ramp testing capabilities, and electrical safety verification for compliance with international electrical standards.
Key Features:
Advanced Testing Capabilities:
Safe voltage measurement function before RCD testing
Large custom digital display readout for clear measurement viewing
Visual indication of reversed phase and neutral wiring at socket
Double molded plastic housing for enhanced durability and insulation
CAT III 1000V safety rating for distribution-level testing
Comprehensive RCD Testing:
Multiple nominal test currents: 10mA, 30mA, 100mA, 500mA, 1A
Current selection options: 0.5x, 1x, 2x, 5x nominal current
Trip time measurement across different current multipliers
Ramp test function: 0.4x to 1.4 times nominal rated current
Mains voltage measurement: 230V (+10%/-10%) range
Technical Specifications:
Nominal Test Current:
Ranges: 10mA / 30mA / 100mA / 500mA / 1A
Accuracy: (-2% + 10%) + 6 Digits
Trip Time Measurement:
0.5x nominal current: 10-2000 ms range, 1 ms resolution
1x nominal current: 10-500 ms range, 1 ms resolution
2x nominal current: 10-150 ms range, 1 ms resolution
5x nominal current: 10-40 ms range, 1 ms resolution
Accuracy: ±(2% reading + 2 Digits)
Ramp Test Function:
Range: 0.4x to 1.4 times nominal rated current
Resolution: 10%
Mains Voltage Measurement:
Range: 230V (+10%/-10%)
Resolution: 1V
Accuracy: ±(2% reading + 2 Digits)
Physical Specifications:
Size: 200mm x 92mm x 50mm (H x W x D)
Weight: 582g
Safety & Compliance:
Safety Standard: EN 61010-1 CAT III 1000V
EMC & LVD Standards:
EN 61326
EN 61010-1
EN 61010-02-032
EN 61010-02-033
CE Certified
Professional Applications:
RCD trip time testing and verification
Residual current device compliance testing
Electrical installation safety inspections
RCD ramp testing for performance evaluation
Voltage measurement before RCD testing
Wiring verification and fault diagnosis
Testing Functions:
1. Standard Trip Test:
Tests RCD at 0.5x, 1x, 2x, and 5x nominal current
Measures exact trip time in milliseconds
Verifies compliance with required trip times
2. Ramp Test:
Gradually increases current from 0.4x to 1.4x nominal rating
Determines actual trip current level
Identifies marginal RCD performance
3. Voltage Verification:
Checks mains voltage before testing
Ensures safe testing conditions
Prevents testing on incorrect voltages